Off-Grid Solar System Design Calculator

What this calculator does: You list the devices you want to run and how many hours a day each one runs. The calculator adds up your daily energy use, then estimates the solar panels, charge controller, inverter and battery bank needed to cover it. An optional “Adjust system assumptions” section lets you change the panel size, battery voltage, overall system efficiency, battery type, days of autonomy, inverter efficiency and how many devices run at the same time.

Who it’s for: Homesteaders, cabin builders and anyone planning a stand-alone (off-grid) solar system who wants a realistic starting number before pricing equipment or talking to an installer.

The answer it produces: Your daily energy use in kWh, a panel count and charge controller size for both summer and winter, an inverter size in kW, and the rated battery bank size in kWh for the days of autonomy you choose. The starting assumptions are 400 W panels, a 48 V battery bank, 75% overall system efficiency, a lithium battery, 2 days of autonomy and 90% inverter efficiency. If the winter sun estimate falls below 2 peak sun hours, it adds a low-winter-sun warning.

Important limitation: This is a planning estimate, not a system design. It allows for real-world losses with one overall efficiency figure (75% unless you change it) and gives the rated battery capacity you shop for, but it does not model shading, panel tilt and direction, temperature effects, the controller’s maximum panel voltage or motor start-up surges. The optional panel string voltage check under the calculator handles the voltage limit separately. It also sizes panels to cover your full daily use in each season, which for the winter figure can mean a large array. The sections below show how to check each one.

Extras built in: quick-add buttons for common appliances (fridge, freezer, well pump, lights, mini-split and more), a battery bank size in amp-hours, the number of 100 A charge controllers you would need, a Use my location button that fills in your latitude, and an optional panel string voltage check for cold mornings. Want to see these numbers on a real build? Jump to our own 18.6 kW off-grid design.

Off-Grid Solar Sizing Calculator

For a more location-specific estimate, enter your latitude below. If you leave it blank, we’ll provide a generalized average estimate.

Used only if you don’t enter a latitude below. If unsure, 4–5 is a reasonable default for much of the continental U.S.

Enter your latitude for more location-specific summer and winter estimates. If you don’t know your latitude, you can leave this blank and the calculator will use an average estimate.

Example: Norfolk, Virginia ≈ 36.85° N (enter as 36.85; Southern Hemisphere locations use a negative number, e.g. -33.87)

Adjust system assumptions (optional)

Used for the charge controller current. A higher voltage means lower current for the same power.

Panels rarely deliver their full rating. Dirt, shading, wiring, heat, the charge controller, battery round-trip losses, and the inverter all take a share. About 75% is a typical planning figure for an off-grid system with batteries.

How many days the batteries should carry your loads with little or no sun.

100 assumes everything runs at once, which is the safe choice for sizing an inverter. Enter less only if you are sure some loads never overlap.

Want to save your design and keep working on it?

The Off-Grid Solar System Design Workbook (Excel & Google Sheets) uses the same math as this calculator, but you can save it, change any number later and plan the whole build in one place: your appliance list, summer and winter panel counts, charge controllers, battery bank in kWh and amp-hours, inverter and surge, the cold-weather string check, and a parts and cost list that updates as you go.

Get the Workbook, $19Or get it with both solar guides and the Homestead Planner, $34.99 →

Off-grid house with rooftop solar panels

How the Calculation Works

Every time you press Calculate, the tool checks your entries and then runs the same five steps. It is plain arithmetic that you can check with a pencil, and the math runs in your browser.

  1. Daily energy use. For each device, watts × hours used per day = watt-hours (Wh). Add every device together and divide by 1,000 for kWh per day. This is the same load-analysis method the U.S. Department of Energy describes: multiply each appliance’s wattage by the hours it runs each day.
  2. Peak sun hours. One peak sun hour is one hour of sunlight at full strength (1,000 W per square meter), so “4 peak sun hours” means the day’s total sunlight adds up to four hours of full-strength sun. If you enter a latitude, the tool estimates the sunlight on a flat, horizontal surface for the June and December solstices from solar geometry (sun angle and day length), then multiplies by a fixed clearness factor of 0.55 to allow for typical atmosphere and cloud. If you leave latitude blank, it takes the peak sun hours you entered (default 5) and multiplies by 1.25 for summer and 0.75 for winter.
  3. Solar panels. Panels = daily Wh ÷ (panel watts × peak sun hours × overall system efficiency), rounded up to the next whole panel. The defaults are 400 W panels and 75% efficiency. It is calculated separately for summer and winter.
  4. Charge controller. Amps = (panels × panel watts ÷ battery voltage) × 1.25, rounded up. In other words, total array watts divided by the battery bank voltage, with a 25% margin on top. The battery voltage defaults to 48 V.
  5. Inverter and battery bank. Inverter kW = the combined wattage of every device you listed × the share running at once (100% by default) × 1.3 for 30% headroom. Battery kWh = daily kWh × days of autonomy ÷ (usable depth of discharge × inverter efficiency). The defaults are lithium at 90% usable, 90% inverter efficiency and 2 days, so this is the rated capacity to shop for, not just the energy you can use.

Inputs and Assumptions

These are the fields you fill in:

InputWhat to enterNotes
Device nameAny label you likeFor your reference only. It does not affect the math.
Wattage (W)Running watts for the deviceUse the nameplate or, better, a plug-in watt meter. Every device you list adds to the inverter size, even one with 0 hours, so list only what you actually plan to run.
Hours used dailyAverage hours per day the device draws that wattageQuarter-hour steps are allowed, up to 24. For cycling loads like refrigerators, use real run time, not 24 hours.
Peak sun hoursYour area’s average, default 5Used only when latitude is left blank. Must be between 1 and 12.
Latitude (optional)Decimal degrees, such as 36.85Use a negative number in the Southern Hemisphere. Degrees-and-minutes formats are not accepted, and a value outside -90 to 90 shows an error.
Solar panel size (W)Default 400Under Adjust system assumptions. 50 to 1,000.
Battery system voltage12, 24 or 48 V, default 48Used for the charge controller current.
Overall solar system efficiency (%)Default 7530 to 100. Covers dirt, shading, wiring, heat, the charge controller, battery round-trip losses and the inverter.
Battery typeLithium (about 90% usable) or lead-acid (about 50%), starts on lithiumSets the usable depth of discharge.
Days of battery autonomyDefault 2More than 0 and up to 10, in half-day steps.
Inverter efficiency (%)Default 9050 to 100.
Share of devices running at the same time (%)Default 10010 to 100. 100 is the safe choice for sizing an inverter.

And these are the assumptions built into the tool. The first five can be changed in the assumptions section, and the rest are fixed:

AssumptionValue used
Panel size400 W each (editable)
Battery bank voltage (for controller amps)48 V (editable)
Overall system efficiency75% (editable)
Battery type and autonomyLithium at 90% usable, 2 days, with 90% inverter efficiency (all editable)
Devices running at once100% (editable)
Inverter headroomListed watts × share running at once × 1.3 (fixed)
Charge controller margin25% (fixed)
Clearness factor (latitude mode)0.55 (fixed)
Seasonal swing (no latitude)Summer +25%, winter −25% around your average (fixed)
Panel string voltage check (optional)Uses the panel Voc and temperature coefficient from your spec sheet, your coldest expected temperature and your controller limit, all entered by you (coefficient starts at −0.27%/°C, limit at 150 V)
Not includedShading, panel tilt and direction, temperature effects, the controller’s maximum panel voltage, motor start-up surge

What the Result Means

  • Total daily usage (kWh). The energy your system must generate and store every day. Every other number scales from this one, so it is the most important figure to get right.
  • Summer and winter panel counts. How many panels of your chosen size are needed to cover your full daily use in each season, after the overall system efficiency. Buy against the winter figure, because a system sized for summer runs short in the darkest months.
  • Estimated peak sun hours. The sunlight the tool assumed for each season. If these look far too high or too low for your region, check them against measured data (see the sources below).
  • Charge controller (amps). The current the array would push toward your battery bank, with a 25% margin, rounded up. It is a starting point for comparing controllers, not a final selection, because it says nothing about the controller’s maximum panel voltage.
  • Battery amp-hours and controller count. Below the main results, the tool converts the battery bank to amp-hours at your battery voltage (kWh × 1,000 ÷ volts) and divides the larger seasonal controller figure by 100 A to show how many 100 A controllers it takes. Each controller needs its own share of the panel strings.
  • Inverter (kW). A continuous AC rating that could carry the share of your listed devices you said run at once, with 30% to spare.
  • Battery bank (kWh). The rated capacity to shop for, covering your days of autonomy after allowing for the usable depth of discharge and inverter efficiency (see the example below). The line above it in the results says which assumptions it used.
  • Low winter sun warning. A yellow box appears if the winter estimate is under 2 peak sun hours. It means covering all your winter use with panels alone takes a very large array.
  • Red error messages. A latitude outside -90 to 90, an assumption outside its allowed range, hours over 24, or no device with a wattage and hours stops the calculation and names the problem.

Example Calculation

Here is a small-cabin load list run through the calculator at 36.85° N latitude, the Norfolk, Virginia example used in the tool. The devices and wattages are illustrative, not a recommendation, so measure your own.

DeviceWattsHours per dayWh per day
Refrigerator15081,200
LED lighting605300
Laptop606360
Well pump7501750
Internet router1224288
Total1,0322,898

The tool then works out the following (it displays peak sun hours rounded to one decimal, but the math uses the unrounded values):

OutputResultHow it is calculated
Daily usage2.90 kWh2,898 Wh ÷ 1,000
Inverter1.34 kW1,032 W × 1.3
Battery bank (2 days, lithium)7.16 kWh2.898 kWh × 2 ÷ (0.9 × 0.9)
Summer (6.4 peak sun hours)2 panels, 21 A2,898 ÷ (400 × 6.38 × 0.75) = 1.51, rounded up to 2 panels; 800 W ÷ 48 V × 1.25 = 20.8 A, rounded up
Winter (2.4 peak sun hours)5 panels, 53 A2,898 ÷ (400 × 2.36 × 0.75) = 4.09, rounded up to 5 panels; 2,000 W ÷ 48 V × 1.25 = 52.1 A, rounded up

Adjusting the example for the real world. The 75% overall efficiency is what turns the winter answer from 4 panels into 5. Four panels would produce about 3,780 Wh on an average December day (400 W × 4 × 2.36), roughly 30% above the 2,898 Wh needed, but only about 2,835 Wh after 25% losses, just under what the cabin needs. The 75% figure is our own planning allowance, not a published one, and NREL’s PVWatts tool asks for an overall system-losses percentage for the same reason. If you set the efficiency to 100%, the winter answer drops to 4 panels and the controller to 42 A, so change it only if you have measured data.

The battery figure now includes the depth of discharge. Two days of this cabin’s use is 5.80 kWh of energy. With lithium at 90% usable and a 90% efficient inverter, the rated capacity to shop for is 5.80 ÷ 0.81 = 7.16 kWh. Choose lead-acid at 50% usable and it becomes 12.88 kWh, and asking for 3 days of autonomy on lithium raises the lithium figure to 10.73 kWh. Check your own battery’s datasheet for the depth of discharge it allows.

The 1.34 kW inverter figure covers the running load of everything listed. If you know some devices never run together, lower the share running at once, for example to 60%, and it becomes 0.80 kW, but the well pump is a motor, and motors can draw several times their running wattage for a moment at start-up, so check the pump’s nameplate and the inverter’s surge rating before you choose one.

Battery voltage changes the controller current, not the panel count. The five winter panels (2,000 W) on a 24 V bank need 105 A and on a 12 V bank 209 A, against 53 A at 48 V. If your panels are 300 W instead of 400 W, the winter answer becomes 6 panels (1.8 kW) and 47 A on a 48 V bank.

Typical Off-Grid Solar System Sizes: Cabin, Home and Homestead

These rows run three daily loads through the calculator’s default settings (400 W panels, a 48 V lithium bank, 75% overall efficiency and 2 days of autonomy) at 36.85° N, the same Norfolk, Virginia latitude as the example above. They show scale only. Your own loads and location will change every number.

ExampleDaily usePanels (summer / winter)Battery bank (2 days)Charge controller (winter)
Small cabin: lights, fridge, laptop, router, small well pump3 kWh2 / 5 panels (2.0 kW)7.4 kWh, about 155 Ah at 48 V53 A, one 100 A controller
Efficient off-grid home10 kWh6 / 15 panels (6.0 kW)24.7 kWh, about 515 Ah at 48 V157 A, two 100 A controllers
Homestead with freezers, well pump and shop20 kWh11 / 29 panels (11.6 kW)49.4 kWh, about 1,029 Ah at 48 V303 A, four 100 A controllers

Inverter size depends on which devices run at the same time, not on daily kWh, so it is left out of this table. The homestead row lands close to our own design, which also uses four 100 A controllers.

Panel String Voltage Check: How Many Panels Can Go in Series?

A solar panel’s voltage rises as it gets colder. Spec sheets list the open-circuit voltage (Voc) at 25°C (77°F), but on a freezing, sunny morning a string of panels can push well above that. If the string goes over the charge controller’s maximum PV input voltage, the controller can be damaged. The optional check under the calculator does this math for you:

  • Cold Voc per panel = Voc × (1 + temperature coefficient ÷ 100 × (coldest °C − 25))
  • Most panels in series = controller maximum PV voltage ÷ cold Voc per panel, rounded down

Our own example: our 580 W panels have a Voc of 51.65 V. With a typical coefficient of −0.27%/°C and a 0°F (−17.8°C) morning, each panel reaches about 57.6 V. Two in series is about 115 V, under the LiTime controller’s 150 V limit, while three would reach about 173 V. That is why our 32 panels run as 16 two-panel strings. Use the coefficient from your own panel’s spec sheet. Some controller makers ask for extra margin below the maximum, and the National Electrical Code (Article 690.7) sets the official method, so check your manual and local code too.

How to Use the Result in a Real System

  1. Cut loads before you size. Every watt-hour you avoid saves panels, battery and inverter. The Department of Energy makes the same point: efficiency improvements first mean a smaller, cheaper system. Our guide to energy-efficient off-grid appliances is a good place to start.
  2. Size panels from the winter number and check the efficiency. The tool already applies a 75% overall efficiency. NREL’s PVWatts tool asks for an overall system-losses percentage for the same reason, and an installer can refine the figure for your equipment and site.
  3. Check the battery figure against the datasheet. The tool’s kWh is a rated capacity based on the battery type you chose. Confirm the depth of discharge your battery allows and the bank voltage you plan to use.
  4. Check the inverter two ways. The continuous rating should meet the calculator’s kW figure, and the surge rating should cover your largest motor start-up. Running big loads one at a time lets a smaller inverter do the job, so lower the share running at once only when you are sure of it.
  5. Match the charge controller to your actual array. Use the amp figure, which already includes a 25% margin, to shortlist controllers, then check each datasheet for maximum panel input voltage and maximum panel power. Panel voltage rises in cold weather, so the wiring layout of your panels matters here. Use the panel string voltage check under the calculator to see how many panels can safely go in series.
  6. Cross-check your sun hours against measured data. Compare the tool’s estimate with NREL’s solar data for your location (links below).
  7. Plan for cloudy stretches. Two days of battery is the starting point, and you can change the days of autonomy. Decide whether a generator or extra battery makes sense for your climate, and see how long your bank will actually last with our battery bank runtime calculator.
  8. Get the wiring and protection right. Wire sizes, fuses, breakers and disconnects must follow the National Electrical Code and your local rules. Have a qualified electrician or solar installer review the design before you buy or connect anything.

Our Own Off-Grid Solar Design (Being Built)

Status: planned and under construction, not yet installed or tested. This is the system Mike is building for the homestead in southeast Virginia. Everything below is design math from the spec sheets, not measured results. Once it is running, we will log real battery data through the Victron Cerbo GX and solar production from the charge controllers, and we will update this section with actual numbers, including what winter really looks like.

ComponentQtyWhat it adds up to
Philadelphia Solar 580 W bifacial panels32About 18.6 kW of panels (32 x 580 W = 18,560 W), as 16 two-panel strings
16 kWh LiFePO4 battery boxes (EVE MB31 314 Ah cells, JK 200 A BMS)4About 64 kWh nominal at 48 V (4 x 314 Ah x 51.2 V)
Victron MultiPlus-II 48/5000 inverter-chargers28 kW continuous (4 kW each), 9 kW surge each, split-phase 120/240 V
LiTime 100 A MPPT charge controllers (built-in heatsink and fan, optional DIY water cooling), fed by 2 MidNite MNPV12 combiners with a 30 A MidNite breaker on every string4 (one is already in service; 3 more to buy)Up to 400 A of charging; each unit is rated for up to 6,000 W of PV at 48 V and a maximum of 150 V input
Victron Cerbo GX MK2 system controller1Monitoring, remote access through VRM, generator auto-start
600 A busbar kit1DC distribution between batteries, inverters and controllers

What the math taught us before a single panel went up

  • The charge controllers, not the panels, set the ceiling. To use the whole 18 kW array on a 48 V battery bank, we need roughly 300 A of charge-controller capacity (300 A x 57.6 V is about 17 kW). For scale, Victron rates its MPPT RS 450/100 at about 5.8 kW of charge power (Victron specifications), so a single 100 A controller would leave most of the array unused at midday.
  • Charge controllers are a hidden big-ticket item. Panels and batteries get the attention, but 300 A or more of 48 V charge-controller capacity can be one of the most expensive parts of a build this size. Two Victron SmartSolar MPPT RS 450/200 units would give 400 A through eight independent trackers, accept 450 V strings and report straight to Victron’s VRM portal, at $2,132.65 each (our November 2026 quote), or $4,265.30. We chose four LiTime 100 A MPPT controllers instead, at about $248 each on LiTime’s own site (November 2026): roughly $990 for the same 400 A. Because the LiTime’s 150 V input limit means short two-panel strings (about 103 V open-circuit at standard test conditions, leaving room for the rise on cold mornings), we combine them in two MidNite MNPV12 combiners (each splits to feed two controllers), with a MidNite MNEPV30 breaker on every string and a MidNite surge protector for each controller. That protection gear runs about $1,050, but any array this size needs disconnects and surge protection whichever controllers you choose, so the real difference is the controllers themselves: about $990 versus $4,265 for the Victron pair, roughly $3,270 less.
  • Saving that money came with trade-offs we accepted on purpose. The LiTime takes a maximum of 150 V of PV input, so the 32 panels will run in short two-panel strings through combiner boxes instead of a few long strings, which means more fuses and heavier PV wiring. Its solar production also will not show up in VRM automatically, so we will track it from the controllers themselves through LiTime’s Bluetooth app. Each unit already has a cast aluminum heatsink and a cooling fan, so it needs no custom cooling to run. If we want the controllers cooler and quieter indoors, the plan is to weave 3/8 inch copper tube through the rear heat sinks, manifold the four units together and add a circulation pump, which is cheaper and simpler than fitting a custom water block to each unit. We first planned on BettSun controllers with custom water blocks (about $840 for four) and switched to the LiTime before buying.
  • Four controllers at about 70% load, with spares to follow. An 18 kW array usually delivers around 14 to 15 kW at real-world peak, and four 100 A controllers can take about 21.6 kW at typical 48 V charging voltage, so each should run at roughly 70% of its rating. Once the system has been thoroughly tested, we plan to add two spare controllers. If one fails, the other three carry the array until we swap in a spare the same day, instead of waiting weeks on a warranty repair. Even with both spares added later (six units, about $1,490), the controllers would come in about $2,780 under the Victron pair.
  • The inverters decide what can run at once. A 64 kWh battery bank can store a lot of energy, but two MultiPlus-II units deliver 8 kW continuous. Big loads like a well pump, heat pump and shop tools have to be planned so they don’t all start together.
  • Every number on the spec sheet has to agree. Panel watts, controller limits, battery voltage and inverter output all have to fit. Sizing panels alone, which is what most simple calculators do, would have hidden the controller bottleneck completely.

Use the calculator above for your own loads, then check each answer against the real limits of the equipment you plan to buy: controller charge power, inverter continuous watts and battery voltage. To see how long a bank like ours would carry your loads, try the Battery Bank Runtime Calculator.

Important Variables That Can Change the Result

  • Latitude and local climate. Sunlight varies with location, season and weather, and the tool applies one fixed clearness factor everywhere. A foggy coastline and a dry high desert at the same latitude will not produce the same energy.
  • Panel tilt and direction. The tool never asks about either. A fixed panel angled toward the sun captures different energy than the flat-surface estimate the calculator uses.
  • Shading. Trees, roof edges and even a chimney can cut a panel string’s output sharply, well beyond the area of the shadow.
  • Temperature. Hot panels produce less, and cold panels produce higher voltage, which matters for charge controller compatibility.
  • Panel wattage. The tool starts at 400 W panels and lets you enter a different size. Bigger panels mean fewer of them for the same array watts.
  • System voltage. Controller amps are calculated for the voltage you choose, 48 V by default. The same array on a 24 V bank carries about double the current, and on a 12 V bank about four times.
  • Days of autonomy. The tool uses two days unless you change it, and the battery figure scales in direct proportion.
  • Battery chemistry and depth of discharge. This decides how much rated capacity you need for a given usable figure, and lead-acid needs about 1.8 times the rated capacity of lithium.
  • Conversion losses. Wiring, the charge controller, the inverter and battery charging and discharging all lose some energy along the way. The tool uses one overall efficiency for the panels and a separate inverter efficiency for the battery.
  • How your household uses power. A winter heating fan, a summer cooling load or a well pump that runs more in dry weather can shift your real daily use away from the average you entered.

Common Mistakes

  • Guessing wattage and hours. A plug-in watt meter over 24 hours gives you real numbers for a refrigerator or freezer, which cycle on and off. Entering 24 hours at full wattage overstates it, and forgetting standby draw understates it.
  • Sizing to the summer figure. Summer output is the easy case. Winter is when systems fail.
  • Leaving lithium selected when you are buying lead-acid. The default assumes lithium at 90% usable. Lead-acid at 50% usable needs about 1.8 times as much rated capacity.
  • Setting the system efficiency to 100%. Without a loss allowance, a system that looks adequate on paper often comes up short in winter.
  • Lowering the share running at once without checking. If two big loads overlap, the inverter will be too small.
  • Forgetting motor start-up surge. Pumps, compressors and power tools can trip an undersized inverter even when their running wattage looks small.
  • Confusing peak sun hours with daylight hours. Twelve hours of daylight is not twelve peak sun hours. Typical values are a small fraction of daylight length, so entering daylight hours will badly undersize your system.
  • Entering latitude the wrong way. Use decimal degrees (36.85, not 36°51′), and a negative number south of the equator.
  • Listing seasonal loads year-round. Air conditioning does not run in January. Size for the season that drives your worst case, and use separate runs of the calculator if your loads change a lot.
  • Leaving out electric heat. Resistance heating can dwarf every other load. Plan heat separately with our off-grid heating calculator rather than adding it to a solar system by default.

When This Calculator Should NOT Be Used

  • For a grid-tied or net-metered system. Those systems are sized around your utility bill and utility rules, and usually have no battery.
  • As final design, permit or purchasing documents. It is a planning tool. Code compliance, wiring and protection need a qualified designer.
  • At high latitudes. From about 41° N or S, the tool’s winter estimate falls below 2 peak sun hours and it shows a low-winter-sun warning, and it never returns fewer than 0.5. Above about 50° the December estimate is around one peak sun hour or less. Winter panel counts there become very large and very uncertain, so use measured local data instead.
  • For life-safety or medical equipment. Anything that must never lose power needs professional design, redundancy and backup.
  • For heavy-load properties. Welders, electric heat, EV charging and large motors need a proper engineering load calculation.
  • For DC-direct systems with no inverter. The panel, controller and battery figures still apply, but ignore the inverter size.
  • For hybrid systems with a generator. The tool sizes for solar and batteries alone.

Related Honey Hen Calculators

Related Honey Hen Articles

Authoritative Sources

Off-Grid Solar Calculator FAQ

How many solar panels do I need to go off-grid?

Divide your daily energy use in watt-hours by the panel wattage times your peak sun hours, using the winter figure, then add a margin for losses. In the example above, a cabin using 2.9 kWh a day at 36.85° N needs 5 panels of 400 W at the calculator’s default 75% overall efficiency. It would need 4 if you set the efficiency to 100%, so keep the loss allowance unless you have measured data.

What size battery bank do I need?

The calculator gives the rated capacity for the days of autonomy you choose, 2 by default, after allowing for the battery’s usable depth of discharge and the inverter’s efficiency. For the example cabin that is 7.16 kWh of lithium or 12.88 kWh of lead-acid. Adjust the days of autonomy for your climate and how much risk you are willing to accept.

Why does the calculator show both a summer and a winter result?

Sunlight changes through the year, so the number of panels needed to cover the same daily use changes too. Winter is the limiting case for an off-grid system, so buy panels using the winter figure.

How accurate is the peak sun hour estimate?

It is a geometric estimate with one fixed clearness assumption, not measured weather data. It gives a reasonable starting point and shows the seasonal swing, but local cloud cover, elevation and terrain can move the real number. Compare it with NREL’s solar data for your location before you buy equipment.

Do I need a bigger system for cloudy climates?

Yes. Fewer peak sun hours means each panel produces less energy per day, so you need more panels, more battery, or a backup source such as a generator to cover the same usage. If you leave latitude blank, lower the peak sun hours field to match your climate.

What if I use 24 V or 12 V batteries, or panels that are not 400 W?

Open Adjust system assumptions and enter your panel wattage and choose 12, 24 or 48 V. The panel count and controller amps update to match. The lower the voltage, the higher the current.

Why is the system efficiency set to 75%?

Real panels rarely deliver their full rating. Dirt, shading, wiring, heat, the charge controller, battery round-trip losses and the inverter all take a share. The 75% figure is our planning allowance for an off-grid system with batteries, not a published number, and you can change it under Adjust system assumptions if you have measured data.

How many amp-hours of battery do I need?

Amp-hours = battery kWh × 1,000 ÷ battery voltage. The calculator shows it under the results. The example cabin’s 7.16 kWh works out to about 150 Ah at 48 V, or about 597 Ah at 12 V, which is one reason larger systems use 48 V.

How many solar panels can I put in series?

As many as stay under your charge controller’s maximum PV input voltage on the coldest morning. Use the panel string voltage check under the calculator with your panel’s Voc and temperature coefficient. With a 150 V controller and our 51.65 V panels, the answer is two.

How many charge controllers do I need?

Divide the winter charge controller amps by one controller’s rating and round up, then check that each controller’s share of the panels stays under its maximum PV power and voltage. A 3 kWh cabin needs 53 A, so one 100 A controller. A 20 kWh homestead needs about 303 A, so four.

Can this calculator size a grid-tied system?

No. It is built around off-grid sizing, with panels, batteries, an inverter and a charge controller for full self-sufficiency. Grid-tied systems have different sizing rules and typically do not need battery storage.


Want the full playbook? Practical Off-Grid Solar, our complete plain-English guide, walks through everything on this page in depth — sizing, wiring, safety, and a full real-world case study from our own system — available now in ebook and paperback.

Building a DC-direct system with no central inverter? Our book No Inverter Needed covers the 48V wiring side.

This calculator provides general planning estimates, not an engineering design. Actual system requirements depend on your specific location, equipment efficiency, wiring, code requirements, and installation conditions — consult a qualified solar installer or electrician before purchasing equipment.

How big a solar system do you need? Free off-grid solar calculator from Honey Hen Homestead